TYPE |
Portable, Automatic, Single-Phase Transformer Turns-Ratio Tester |
INPUT POWER |
6 D Cells (250-test capacity) |
MEASUREMENT METHOD |
ANSI/IEEE C57.12.90 |
RATIO-MEASURING RANGE |
0.8 to 15,000 (5-digit resolution) |
TURNS-RATIO ACCURACY |
0.800–1,999 (±0.1%), 2,000–3,999 (±0.25%), 4,000–15,000 (±1.5%) |
TEST VOLTAGES |
8 Vac @ 350 mA, 40 Vac @ 70 mA |
EXCITATION READING RANGE |
0 – 2 Amperes |
CURRENT READING ACCURACY |
±1 Milli-amp, ±2% of reading (±1-digit) |
DISPLAY |
Back-lit LCD screen (4 lines by 20 characters), viewable in bright sunlight and low-light levels |
COMPUTER INTERFACE |
One RS-232C (19,200 baud) port |
PC SOFTWARE |
Windows® XP/Vista-based, included with purchase price |
SAFETY |
Designed to meet IEC61010 (1995), UL61010A-1, CSA-C22.2 standards |
ENVIRONMENT |
Operating: -10˚C to 50˚C (15˚F to 122˚F); Storage: -30˚ C to 70˚C (-22˚F to 158˚F) |
CABLES |
One 15-foot single-phase cable, one cable-carrying duffel bag included |
OPTIONS |
Transportation case |
WARRANTY |
One year on parts and labor |
Specifications are valid at nominal voltage and ambient temperature of +25˚C (+77˚F). Last updated on February 16, 2009 |