TYPE |
Portable, lightweight, automatic 3-phase transformer turns-ratio meter |
PHYSICAL SPECIFICATIONS |
18”W x 5”H x 12”D (45.7 cm x 12.7 cm x 30.5 cm ); Weight: 20 lbs (9.1 kg) |
OPERATING VOLTAGE |
100 – 240 Vac, 50/60 Hz |
MEASUREMENT METHOD |
ANSI/IEEE C57.12.90 |
TURNS-RATIO MEASURING RANGE |
0.8 – 50,000 to 1 |
TURNS-RATIO ACCURACY |
0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.25%, 4,000 – 14,999: ±1%, 15,000 – 50,000: ±2% @ 4 Vac 0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.20%, 4,000 – 14,999: ±1%, 15,000 – 50,000: ±1.5% @ 40 Vac 0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.20%. 4,000 – 14,999: ±1%, 15,000 – 50,000: ±1.5% @ 100 Vac 0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.15%. 4,000 – 14,999: ±0.8%, 15,000 – 50,000: ±1.2% @ 250 Vac |
TEST VOLTAGES |
4 Vac @ 1 Amp, 40 Vac @ 200 mA, 100 Vac @ 100 mA, 250 Vac @ 50 mA |
EXCITATION CURRENT READING RANGE |
0 – 2 Amperes; Accuracy: ±0.1 mA, ±2% of reading (±1 mA) |
PHASE-ANGLE MEASUREMENT |
0 – 360 degrees; Accuracy: ±0.2 degree ( ±1 digit) |
DISPLAY |
Back-lit LCD screen (128 x 64 pixels) viewable in bright sunlight and low-light levels |
PRINTER |
Optional built-in 4.5-inch wide thermal printer |
COMPUTER INTERFACES |
Bluetooth, USB port |
EXTERNAL DATA STORAGE |
One USB Flash drive interface port; Up to 999 transformer test records can be stored on a USB Flash drive (not included) |
INTERNAL TEST RECORD STORAGE |
Can store 112 transformer test records internally. Each record holds the test record header and up to 99 readings. |
INTERNAL TEST PLAN STORAGE |
Can store 128 transformer test plans internally. Test plans can be transferred to the unit from the PC via Bluetooth/USB port or via the USB Flash drive interface |
PC SOFTWARE |
Windows®-based Transformer Turns Ratio Analyzer application is included with purchase price |
LOAD TAP CHANGER CONTACT |
240 Vac, 2 Amps |
SAFETY |
Designed to meet UL 61010A-1 and CAN/CSA C22.2 No. 1010.1-92 standards |
ENVIRONMENT |
Operating: -10˚ to 50˚ C (15˚ to +122˚ F); Storage: -30˚ C to 70˚ C (-22˚ to +158˚ F) |
CABLES |
One 15-foot (4.57m) single-phase set, one 15-foot (4.57m) 3-phase set, one 25-foot (7.62m) extension set, one safety ground, one USB, cable bag |
OPTIONS |
Transportation case |
WARRANTY |
One year on parts and labor |
Specifications are valid at nominal voltage and ambient temperature of +25˚C (+77˚F). Last updated on February 16, 2009 |
|