TYPE |
Portable, automatic, CVT turns-ratio tester |
PHYSICAL SPECIFICATIONS |
19.5" x 12" x 17" D (49.5 cm x 30.5 cm x 43.2 cm) |
INPUT POWER |
100 – 120 Vac or 220 – 240 Vac (selectable), 50/60 Hz |
MEASUREMENT METHOD |
ANSI/IEEE C57.12.90 |
RATIO-MEASURING RANGE |
75 – 15,000 (5 digit resolution) |
TURNS-RATIO ACCURACY |
75 - 4,999: ±0.25%, 5,000 – 9,999: ±0.35%, 10,000 - 15,000: ±0.5% |
PHASE ANGLE READING |
0-360 degrees, ±0.2 degree accuracy |
POLARITY |
In-Phase or Out-of-Phase indication |
TEST VOLTAGE |
7440Vac @ 50ma |
DISPLAY |
Back-lit LCD (128 x 64 pixels), viewable in direct sunlight and low light levels |
COMPUTER INTERFACE |
RS-232C |
PC SOFTWARE |
Windows XP/Vista/7 Transformer Analysis Software (included with purchase) |
INTERNAL TEST RECORD STORAGE |
128 test records. Each record contains 33 readings. |
EXTERNAL TEST RECORD STORAGE |
Up to 999 test records on external USB Flash drive. |
SAFETY |
Designed to meet IEC 61010A-1 and CAN/CSA C22.2 No. 1010.1-92 Standards |
ENVIRONMENT |
Operating: -10ºC to 50ºC (15ºF to +122ºF) Storage: (-30ºC to 70ºC (-22ºF to +158ºF) |
HUMIDITY (MAX) |
90% RH @ 40˚ C (104˚ F) non-condensing |
ALTITUDE (MAX) |
2000m (6562 ft) to full safety specifications |
CABLES |
One 50 ft. H cable, one 15 ft. X cable, one power cable, one safety ground cable |
WARRANTY |
One year on parts and labor |
Specifications are valid at nominal voltage and ambient temperature of +25˚C (+77˚F). |