TYPE |
Transformer Turns Ratio Tester |
PHYSICAL SPECIFICATIONS |
Dimensions: 12” x 10” x 8” (30.4 cm x 25.4 cm x 20.3 cm) Weight: 8 lbs. (3.6 Kg) |
INPUT POWER |
120 or 240 Vac (Selectable), 50/60 Hz |
MEASURING METHOD |
ANSI/IEEE C57.12.90 |
RATIO MEASURING RANGE |
0.8 - 15,000 (5 digit resolution) |
TURNS-RATIO ACCURACY |
40 Vac: 0.8-1,999 (0.1%), 2,000-3,999 (0.25%), 4,000-15,000 (1%) 4 Vac: 0.8-1,999 (0.1%), 2,000-3,999 (0.25%), 4,000-15,000 (2%) |
TEST VOLTAGE |
4 Vac @ 1.0A, 40 Vac @ 0.6A |
PHASE ANGLE MEASUREMENT |
0 - 360 degrees, Accuracy ±0.2 degree (±1 digit) |
POLARITY READING |
In-Phase or Out-of-Phase indication |
EXCITATION CURRENT READING RANGE |
0-2 Amperes, Accuracy: 2% of reading (±1 mA) |
DISPLAY |
Back-lit LCD (128 x 64 pixels), viewable in direct sunlight and low light levels |
COMPUTER INTERFACE |
RS-232C |
PC SOFTWARE |
Windows XP/Vista/7 Transformer Analysis Software (included with purchase) |
INTERNAL TEST RECORD STORAGE |
128 records of 33 readings |
EXTERNAL TEST RECORD STORAGE |
Up to 999 test records on external USB Flash drive. |
SAFETY |
Designed to meet IEC 61010 (1995), UL 61010A-1, and CSA-C22.2 standards |
ENVIRONMENT |
Operating: -10ºC to 50ºC (15ºF to +122ºF) Storage: (-30ºC to 70ºC (-22ºF to +158ºF) |
HUMIDITY (MAX) |
90% RH @ 40˚ C (104˚ F) non-condensing |
ALTITUDE (MAX) |
2000m (6562 ft) to full safety specifications |
CABLES |
One 15 ft. (4.6m) Single phase cable, one power cord, one cable bag |
OPTIONS |
Transportation Case (Can hold unit and cables) |
WARRANTY |
One year on parts and labor |
Specifications are valid at nominal voltage and ambient temperature of +25˚C (+77˚F). |