Digital Timer

 
       

This product is no longer in production.
  • A built-in Timer displays contact time in both cycles and milliseconds
  • Provides variable AC current source (up to 250 amps)
  • Provides variable AC voltage source (up to 240 Vac)
  • Provides variable DC voltage source (up to 300 Vdc)
  • 24 Vdc, 124 Vdc, 240 Vac power supplies
  • Built-in power resistors
  • Results displayed on a 4-line by 20-character backlit LCD
  • Test current transformer saturation
  • Test transformer turns ratio
  • Timer triggered by voltage transitions, dry-contact
  • Timer trigger output can trigger other RFD-200 or other external devices
       

RFD-200 S2

Technical Specifications

 
       
TYPE Portable relay test set
INPUT POWER 100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz
PHYSICAL SPECIFICATIONS 16.8”W x 12.6”H x 12”D (42.7 cm x 32.0 cm x 30.5 cm); Weight: 35 lbs (15.9 kg)
AMPERE METER INPUT RANGES Internal input range: 0 – 250 A; Accuracy: 2% of reading ± 10 mA,
External AC input range: 0 – 6A; Accuracy: 1% of reading ± 10mA
External DC input range: 0 – 6A; Accuracy: 0.5% of reading ±1 count
Measurement Method: True RMS for AC
VOLT METER INPUT RANGE 0 – 600.0V; AC accuracy: 1% of reading ±1 count; DC accuracy 0.5% of reading ±1 count
Measurement Method: True RMS for AC
AUXILIARY POWER SUPPLIES 24 Vdc @ 1 A, 124 Vdc @ 0.25 A, 240 Vac @ 0.125 A
SAFETY Designed to meet IEC61010 (1995), UL61010A-1, CSA-C22.2 standards
ENVIRONMENT Operating: -10˚C to 50˚ C (15˚F to +122˚ F); Storage: -30˚ C to 70˚ C (-22˚F to +158˚ F)
OPTIONS Transportation case
WARRANTY One year on parts and labor
AC Current Output
Range No-Load Voltage Load Voltage Load Current Load/Unload Times
10 A 90 Vac 75 Vac 10 A 2 min / 15 min
40 A 25 Vac 20 Vac 40 A 1 min / 15 min
100 A 10 Vac 7.25 Vac 100 A 1 min / 15 min
100 A 10 Vac 3 Vac 250 A 1 sec / 5 min
AC Voltage Output
Range No-Load Voltage Load Voltage Load Current Load/Unload Times
250 Vac 260 Vac 240 Vac 3 A 10 min / 45 min
DC Voltage Output
Range No-Load Voltage Load Voltage Load Current Load/Unload Times
300 Vdc 300 Vac 250 Vdc 2 A 10 min / 45 min
Maximum Current
0.4 A
RFD-200 Timer Second Display In seconds and cycles (50/60 Hz programmable)
Range Resolution Accuracy
0 to 9.999 sec 1 ms ± (1 ms + 0.01%)
10.00 to 99.99 sec 10 ms ± (10 ms + 0.01%)
100.0 to 999.999 sec 100 ms ± (100 ms + 0.01%)
Timer Cycles Display
Range Resolution Accuracy
0 to 9.999 cycles 0.1 cycle ± (0.1 cycle + 0.01%)
1,000 to 49,999 cycles / 50 Hz 1 cycle ± (1 cycle + 0.01%)

The RFD-200 Digital Timer can be started or stopped in three different modes:

  1. Internal Trigger: Start timer with the presence or removal of RFD-200 voltage or current source.
  2. Dry Contact: Change of state of a dry contact input.
  3. Wet Contact: Change of state of a DC voltage input.
Specifications are valid at nominal voltage and ambient temperature of +25˚C (+77˚F).