Login for Software/Firmware Downloads

To prevent automated spam submissions leave this field empty.
       

PCI-600

Primary Current Injection Device

 
       
9029-UC [110V PCI-600]
9058-UC [220V PCI-600]

The VIC Model PCI-600 is a programmable, high-current source that is designed specifically for utility-substation applications. This alternating current(ac) test device is used primarily for injection testing of protective relays. This same device can also be used for testing thermal, magnetic and solid-state motor-protection relays and molded-case circuit breakers. The PCI-600 is versatile and can also be used in many other applications that require a high-current source.

  • Results displayed on a 4-line by 20-character backlit LCD
  • Test currents from 10 to 600 amperes
  • Also has an external-current input (0-10 A)
       

PCI-600

Cables

 
       
       

PCI-600

Technical Specifications

 
       
TYPE 10 – 600 Amp current source
PHYSICAL SPECIFICATIONS 16.8”W x 12.6”H x 10.6” D (42.6 cm by 32.0 cm by 27 cm); Weight: 46lbs (21kg)
INPUT POWER 100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz
INTERNAL CURRENT METER 100 mA – 1000 A; Accuracy: 1% of reading, ±20 mA
MEASURING METHOD Isolated CT
EXTERNAL METER RANGE 10 mA – 10 A; Accuracy: 1% of reading, ±2 mA
MEASURING METHOD Isolated CT
TIMER READING RANGE 1 ms – 2 hours; Accuracy: 0.1% of reading ±1ms
TIMER STOP INPUT Voltage input (24 – 300 V, DC or peak AC), dry-contact input, or removal of primary current
COMPUTER INTERFACE RS-232C port (19,200 baud) for factory calibration and diagnostics
SAFETY Designed to meet IEC61010 (1995), UL 61010A-1, CSA-C22.2 standards
ENVIRONMENT Operating: -10˚C to 50˚ C (15˚F to +122˚ F); Storage: -30˚ C to 70˚ C (-22˚F to +158˚ F)
CABLES 10-foot #1/0 AWG test leads, power cord, ground cable
OPTIONS Transportation case
WARRANTY One year on parts and labor
Specifications are valid at nominal voltage and ambient temperature of +25˚C (+77˚F).