Current Transformer Test Set

 
       
9027-UC [110V]
9044-UC [220V]
This product is no longer in production.
  • Perform Saturation, Ratio and Polarity Tests
  • Perform CT Winding Resistance Test
  • Fully Automated
  • Test record header information including company, substation name, circuit ID, manufacturer, CT serial number, operator name, and test record-comments
  • Plot Multiple Saturation Curves
  • Store 140 Records (of 10 Saturation Curves)
  • Computer Interface
  • USB Flash drive interface
       

EZCT-2000A

Cables

 
       
       

EZCT-2000A

Technical Specifications

 
       
TYPE Portable current-transformer test set
PHYSICAL SPECIFICATIONS 16.8”W x 12.6”H x 14”D (42.7 cm x 32.0 cm x 35.6 cm); Weight: 60 lbs (27.2 Kg)
INPUT POWER 100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz
MEASUREMENT METHOD ANSI/IEEE C57.12.90, IEC 60044-1 and ANSI/IEEE C57.13.1
OUTPUT TEST VOLTAGES 0 – 50 Vac @ 10A max,
0 – 300 Vac @ 10A max,
0 – 500 Vac @ 5A max,
0 – 1200 Vac @ 2A max,
0 – 2000 Vac @ 1.2 A max
VOLTAGE READING RANGE 0 – 2,200 Vac; Accuracy: ±1.0% of reading, ±1 volt
CURRENT READING RANGE 0 – 10A; Accuracy: ±1.0% of reading, ±0.02A
CURRENT-RATIO RANGE 0.8 – 999: 0.1%, 1000 – 1999: 0.3%, 2000 – 5000: 1%
PHASE ANGLE MEASUREMENT 0 – 360 degrees; Accuracy: ±1.0 degree
RESISTANCE READING RANGE 100 micro-ohms – 10 ohms; Accuracy: 2% of reading, ±1 count, ±10 μ-ohms
DISPLAY Back-lit LCD Screen (240 x 128 dot graphic; 114mm x 64mm); viewable in bright sunlight and low-light levels
PRINTER Built-in 4.5-inch wide thermal printer
COMPUTER INTERFACES One RS-232C port (115k baud), One USB port
EXTERNAL DATA STORAGE One USB Flash drive interface port
(Flash drive not included)
PC SOFTWARE Windows® XP/Vista-based CT Analysis software is included with purchase price
INTERNAL TEST RECORD STORAGE Stores 140 test records. Each test record may contain up to 10 sets of excitation, resistance and ratio data
INTERNAL TEST PLAN STORAGE Stores 128 test plans. Each test plan can store 10 excitation test voltage and current settings
SAFETY Designed to meet UL 61010A-1 and CAN/CSA C22.2 No. 1010.1-92 standards
ENVIRONMENT Operating: -10˚ to 50˚ C (15˚F to +122˚ F);
Storage: -30˚ C to 70˚ C (-22˚F to +158˚ F)
CABLES Five 20-foot X cable sets, One 35-foot H cable set, power cord, One cable-carrying duffel bag
WARRANTY One year on parts and labor
Specifications are valid at nominal voltage and ambient temperature of +25˚C (+77˚F).