CT-7000 S3

Digital Circuit Breaker Analyzer

 
       
9021-UC [CT-7000 S3 with 3 Contact Channels]
9100-UC [CT-7000 S3 with 6 Contact Channels]
9021-SC [CT-7000 S3 Shipping Case]
9021-DG [CT-7000 S3 Dual Ground Option]
9021-OT [CT-7000 S3 Online Timing Option]
9021-BT [CT-7000 S3 Bluetooth Option]

The CT-7000 S3 is Vanguard's fourth generation EHV circuit breaker analyzer. The CT-7000 S3 is available with 3 (part number 9021-UC) or 6 contact timing channels (part number 9100-UC). The CT-7000 S3 can fully analyze a circuit breaker's performance by measuring the main contact and resistor contact time, stroke, velocity, over-travel, bounce back and contact wipes. Both contact and motion analysis can be performed on all circuit breaker operations (OPEN, CLOSE, OPEN-CLOSE, CLOSE-OPEN, and OPEN CLOSE-OPEN). The CT-7000 S3's timing window is selectable between 1 second, 10 seconds, and 20 seconds.

  • Fully analyze circuit breaker's performance by measuring main contact and resistor contact time, stroke, velocity, over-travel, bounce back and contact wipes
  • USB computer interface
  • USB Flash drive interface (Flash drive not included)
  • Store up to 200 test records and 100 test plans internally
  • Initiate Breaker Operation
  • Built-in 4.5" wide Thermal Printer
  • Rugged "QWERTY" style membrane keypad
  • Optional "On-line" Timing Mode
  • Optional dual ground testing mode
  • Optional Bluetooth wireless computer interface
       

CT-7000 S3

Cables

 
       
       

CT-7000 S3

Technical Specifications

 
       
TYPE Portable circuit-breaker analyzer
PHYSICAL SPECIFICATIONS Dimensions: 21.5”W x 8”H x 14” D (53 cm x 20 cm x 35 cm)
Weight: 15 lbs (6.8 Kg)
INPUT POWER 100-240Vac, 3A, 50/60Hz
DRY-CONTACT INPUTS 3 channels (9021-UC) or 6 channels (9100-UC). Channel can detect the main contact and resistor contact time.
TIMING WINDOWS 1 second, 10 seconds, or 20 seconds
TIMING RESOLUTIONS ±50 micro-seconds @ 1 sec. duration,
±500 micro-seconds @ 10 sec. duration,
±1.0 milli-seconds @ 20 sec. duration
TIMING ACCURACY 0.05% of reading ±0.05 ms @ 1 second duration
DRY-CONTACT CHANNEL PROTECTION All contact inputs are grounded until test. Input channels are also protected against static discharge.
DRY-CONTACT DETECTION RANGE Closed: Less than 20 Ohm. Opened: greater than 5000 ohm
INSERTION RESISTOR DETECTION RANGE 50 – 5,000 ohms
TRIGGER INPUT VOLTAGE Open/Close trigger voltage: 24 V – 300V DC or peak AC
VOLTAGE SENSING INPUT RANGE V1: analog input; 0 – 250 V DC or peak AC; sensitivity ±1 V; record and print voltage level
V2 and V3: voltage presence/absence detector input; 24 – 255 V DC or peak AC; record and print 3 timing events
BREAKER OPERATIONS Initiate Open, Close, Open-Close, Close-Open, Open-Close-Open
BREAKER INITIATE CAPACITY 30A, 250 Vac/dc max
INITIATE CURRENT READING RANGE one, non-contact, Hall-effect sensor, 0 – 20 amp range, dc to 5 Khz AC
DIGITAL TRAVEL TRANSDUCER INPUTS 3 channels, 200 ohm – 10K ohms
CONTACT TRAVEL POINT DIFFERENCE measures “slow-close” contact-point distances; results can be printed
DISPLAY back-lit LCD screen (128 x 240 pixels); viewable in bright sunlight and low light
PRINTER built-in 4.5” wide thermal printer that can print both graphic contact travel waveforms and tabulated test results
INTERNAL TEST RECORD STORAGE Store up to 200 test records and 100 test plans
EXTERNAL TEST RECORD STORAGE USB Flash drive interface for external storage of test records and test plans
COMPUTER INTERFACES One USB port, optional Bluetooth wireless interface
PC SOFTWARE Windows® based Breaker Analysis software included with purchase price
CABLES furnished with full set of test leads
OPTIONS transportation cases (available for the CT-7000 S3 and travel transducers), on-line timing mode, dual ground testing mode,
bluetooth interface
SAFETY designed to meet UL 6101A-1 and CAN/CSA C22.2 No 1010.1-92 standards
ENVIRONMENT Operating: -10°C to +50°C (+15°F to +122°F); Storage: -30°C to +70°C (-22°F to +158°F)
HUMIDITY 90% RH @ 40°C (104°F) non-condensing
ALTITUDE 2,000 m (6,562 ft) to full safety specifi cations
WARRANTY one year on parts and labor
Specifications are valid at nominal voltage and ambient temperature of +25˚C (+77˚F).