TYPE |
Portable micro-ohmmeter |
PHYSICAL SPECIFICATIONS |
Dimensions: 18" W x 7"H x 15" D (45.7cm x 17.8cm x 38.1cm) Weight: 19.8 lbs (8.9 Kg) |
INPUT POWER |
100 – 240 Vac, 50/60 Hz |
RESISTANCE READING RANGE |
10 milliohms at 200A to 5 ohms at 1A Typical Accuracy: ±(0.15% of reading + 0.15% FS) at test current of 10-200A |
TEST CURRENT RANGE |
1 Ampere to 200 Amperes (selectable in 1A steps); Thermally protected DC power supply. |
DISPLAY |
Back-lit LCD (128 x 64 pixels), viewable in direct sunlight and low light levels |
KEYPAD |
Rugged, 44-key "QWERTY" membrane keypad |
INTERNAL TEST RECORD STORAGE |
128 test records. Each record can contain up to 64 readings. |
EXTERNAL TEST RECORD STORAGE |
Up to 999 test records on external USB Flash drive |
COMPUTER INTERFACE |
RS-232C |
PRINTER |
Built-in 2.5" wide thermal printer |
PC SOFTWARE |
Windows XP/Vista/7 Analysis Software (included with purchase) |
SAFETY |
Designed to meet IEC 61010 (1995), UL 61010-a, and CAS-C22.2 standards |
ENVIRONMENT |
Operating: -10ºC to 50ºC (15ºF to +122ºF) Storage: (-30ºC to 70ºC (-22ºF to +158ºF) |
HUMIDITY (MAX) |
90% RH @ 40˚ C (104˚ F) non-condensing |
ALTITUDE (MAX) |
2000m (6562 ft) to full safety specifications |
CABLES |
30 ft (9.1 m), #1 AWG test cables, power cord, ground cable |
OPTIONS |
Shipping case, 15 ft test cables, C-Clamp set, Hand Spike Set |
WARRANTY |
One year on parts and labor |