TYPE |
Portable micro-ohmmeter |
PHYSICAL SPECIFICATIONS |
16.8”W X 12.6”H x 12.0”D (42.7 cm x 32.0 cm x 30.5 cm); Weight: less than 21 lbs (9.5 kg) |
INPUT POWER |
100 – 240 Vac, 50/60 Hz |
RESISTANCE READING RANGE |
1 micro-ohm – 300 milli-ohms (1 micro-ohm resolution); Accuracy: ±1% reading, ± 1 count |
TEST CURRENT RANGE |
Thermally-protected DC power supply, 10 Amperes – 100 Amperes |
TEST DURATION |
5 seconds – 120 seconds, selectable |
DISPLAY |
1-inch high back-lit LCD Screen (16 characters by 2 lines); viewable in bright sunlight and low-light levels |
INTERNAL TEST RECORD STORAGE |
Stores and can display last 3 readings |
COMPUTER INTERFACE |
RS-232C port (19,200 Baud) for factory calibration and diagnostics |
SAFETY |
Designed to meet IEC61010 (1995), UL61010A-1, CSA-C22.2 standards |
ENVIRONMENT |
Operating: -10°C to 50° C (15°F to +122° F); Storage: -30° C to 70° C (-22°F to +158° F) |
CABLES |
30-foot (#1AWG) test cables, ground cable, power cord |
OPTIONS |
Transportation case, 15-foot test cables, C-clamps, Handspike |
WARRANTY |
One year on parts and labor |