TYPE |
Low Resistance Micro-Ohmmeter |
PHYSICAL SPECIFICATIONS |
Dimensions: 14”W x 8”H x 12” D (36 cm x 19.4 cm x 30.4 cm) Weight: 7.8 lbs. (3.54 Kg) |
INPUT POWER |
100 – 240 Vac, 50/60 Hz |
RESISTANCE READING RANGE AND ACCURACY |
Test Current |
Display Min |
Display Max |
Display Unit |
Resolution |
Accuracy |
10A |
000.0 |
999.9 |
μΩ |
0.1μΩ |
±0.2%±0.2μΩ |
|
1.0000 |
9.9999 |
mΩ |
0.1μΩ |
±0.2%±0.2μΩ |
|
10.000 |
99.999 |
mΩ |
1μΩ |
±0.2%±2μΩ |
|
100.00 |
250.00 |
mΩ |
10μΩ |
±0.2%±20μΩ |
5A |
000.0 |
999.9 |
μΩ |
0.1μΩ |
±0.2%±0.4μΩ |
|
1.0000 |
9.9999 |
mΩ |
0.1μΩ |
±0.2%±0.4μΩ |
|
10.000 |
99.999 |
mΩ |
1μΩ |
±0.2%±4μΩ |
|
100.00 |
999.99 |
mΩ |
10μΩ |
±0.2%±40μΩ |
1A |
00.000 |
99.999 |
mΩ |
1μΩ |
±0.2%±2μΩ |
|
100.00 |
999.99 |
mΩ |
10μΩ |
±0.2%±20μΩ |
|
1,000.0 |
5,000.0 |
mΩ |
100μΩ |
±0.2%±200μΩ |
100mA |
000.0 |
999.9 |
mΩ |
10μΩ |
±0.2%±20μΩ |
|
1,000.0 |
9,999.9 |
mΩ |
100μΩ |
±0.2%±200μΩ |
|
10,000 |
50,000 |
mΩ |
1mΩ |
±0.2%±2mΩ |
10mA |
000.0 |
9.9999 |
Ω |
100μΩ |
±0.2%±200μΩ |
|
10.000 |
99.999 |
Ω |
1mΩ |
±0.2%±2mΩ |
|
100.00 |
500.00 |
Ω |
10mΩ |
±0.2%±20mΩ |
1mA |
00.000 |
99.999 |
Ω |
1mΩ |
±0.2%±2mΩ |
|
100.00 |
999.99 |
Ω |
10mΩ |
±0.2%±20mΩ |
|
1,000.0 |
5,000.0 |
Ω |
100mΩ |
±0.2%±200mΩ |
NOTE: stated accuracy for bi-directional current mode |
BATTERIES |
Rechargeable Li-Ion, 3.7Vdc, 3400 mAh, protected (Qty=4) Charge time: 4 hours |
AUTO POWER DOWN |
Programmable: 30 sec, 1 min, 3 min |
DISPLAY |
Backlit LCD screen (128 x 64 pixels); viewable in bright sunlight and low-light
|
TEMPERATURE |
Operating: -10°C to +50°C (+15°F to +122°F) Storage: -30°C to +70°C (-22°F to +158°F) |
HUMIDITY |
90% RH @ 40°C (104°F) non-condensing |
ALTITUDE |
2,000 m (6,562 ft) to full safety specifications
|
SAFETY |
Designed to meet IEC 61010 (1995), UL 61010-a, and CSA-C22.2 standards |
CABLES |
15 ft (4.57 m) cable set with alligator clamps, power cable, cable bag |
OPTIONS |
30 ft (9.14 m) cable set, 10 ft (3m) hand probe (5A), 10 ft (3m) hand probe (10A), pistol grip probe (10A), shipping case |
WARRANTY |
One year on parts and labor |
Specifications are valid at nominal voltage and ambient temperature of +25˚C (+77˚F). |